TRUSTEC QX3 4000 - 8000

The basis of these inverters are more than 6 decades Production experience electrotechnical devices.

TRUSTEC new three-phase inverter QX 3 are distinguished by the following facts:

  • Highest functional reliability
  • Integrated data logger
  • Web server for online monitoring
  • 3 MPP trackers - quick reactions in relation tosunlight and temperature
  • Integrated ripple control receiver connection
  • For maximum power yields high efficiency
  • Easy installation "Plug and Play"
  • Rapid increase efficiency even at low sunlight, then they run nearly constant over the power range
  • Good planning software
  • Service Hotline 24/7 days
  • Warranty by German manufacturers
  • A value concept that pays off
  • Own consumption optimization
  • Dynamic regulation 70%
  • IP65
  • Large DC input range of 250 V - max. 1000 V enables flexible module design
  • High efficiency up to 98%

 

DC-Input QX3 4000 QX3 5000 QX3 6000 QX3 7000 QX3 8000
DC Power (+15% acc.ISE) 4.700 W 5.800 W 7.000 W 8.700 W 9.500 W
Max. input voltage 1.000 V
Min. input voltage / Start input voltage Input A: 175 V / 200 V
Min. input voltage * Input B: 120 V
MPP voltage range 190-680 V 240 - 680 V 280 - 680 V 260 - 680 V 290 - 680 V
Rated input voltage 600 V
Max. current per input (A/B) ** 10/10 A 18 / 10 A
Max. short ciruit current per input 12 / 12 A 20 / 12 A
Start feeding - in at 20 W
Number of independet MPP inputs 2
Strings per MPP input 1 .2 / 1
DC terminal type SUNCLIX
DC Overvoltage category III        
AC Output QX3 4000 QX3 5000 QX3 6000 QX3 7000 QX3 8000
Rated output power (230V/50Hz,cos.=1) 4.000 W 5.000 W 6.000 W 7.000 W 8.000 W
Max. apparent AC power 4.000 VA 5.000 VA 6.000 VA 7.000 VA 8.000 VA
AC connection 3 / N / PE
AC nominal output voltage range 3x 400 V / 3x 230 V +/- 20 %
Power factor range, adjustable cos. 0,9 ind .... 1 1 ... 0,9 kap.
Operating range at nominal frequency 50 Hz / 47,5 Hz Hz-51,5 Hz
Max. output current 3x 8 A 3x 8 A 3x 10 A 3x 12 A 3x 12 A
Max. short circuit current 3x 8 A 3x 8 A 3x 10 A 3x 12 3x 12
Max. permitted fusing Circuit breaker 16 A, characteristic B
Distortion factor at cos. = 1 < 3 %
Self-consumption at night < 2 W
AC Overvoltage category III
Efficiency          
Max. efficiency / Europen efficiency 97,5 % / 97,0 %
Protection & protective devices          
Topology transformerless
Protection (class) / ingress protection (I) IP 65 (I) IP 54 / connection area IP 65
Earth fault detection integrated
Residual current monitoring integrated, sensitive to universal current
Overload / Overtemperature behaviour operating point adjustment
Input isolator integrated
Overvoltage protection-input & output integrated, type 3 as per EN61643-11
Automatic disconnection device as per VDE 0126-1-1
Environmental conditions          
Cooling concept fan-less varlable speed, temperature-controller fan
Operating temperature range -20 to + 60 °C
Max. amblent temp. at rated power 45 °C 40 ° C
Climatic category 4K4H-according to IEC721-3-4 ***
Noise emission / max. operating altitude < 50 dB (A) / 2000 m above sea level
Standards an approvals          
EMC emission / EMC Immunity EN61000-6-3 : 2001 / EN6100-6-2:2005
Equipment safty / Grid compliance EN 62109-1, -2 / VDE-AR-N 4105
General Data          
Weight (approx.) / Dimensions 25 kg / 360 x 506 x 190 mm
(without plugs)
27 kg / 360 x 506 x 190 mm
(without plugs)
Display liquid crystal display, 128 x 64 pixel
Communication Interfaces (internal) RS485, USB, Ethernet, solar radiation,
S0 as per DIN EN 62053-31 Class B
Data storage 24 h: 5 min values , 30 days: hourly values, 20 years: dally values
Warranty 5 years